Permit: T06CM06432

Parcel: 117091810


Addresses:

1043 S 5TH AV #02

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
08/09/2007 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
07/27/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NOT READY
07/26/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) HAVE INSPECTED UNDERNEATH OF FOAM INSULATION, REBAR PLACEMENT PER DETAIL 9/6
07/17/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) HAVE INSPECTED REBAR LAYOUT IN OFFICE AND LAUNDRY ROOM, EXCEPT ENTRY
2) EVERYTHING OK-OK TO POUR FOOTERS
07/16/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO GET REVISION FOR HORIZONTAL BAR PER DETAILS 2/6 & 12/6 AND CORRECT PLACEMENTS OF VERTICAL BARS-2 EACH 48" ON CENTER OR 1 EACH AT 24" ON CENTER STAGGERED SUFFICIENT