Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2007 | ELECTRIC - UNDERGROUND | Approved | ||
| 03/22/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 16 FEEDS TO MODULARS EA 3 1/0 AL USE & #6 GRU AL USE OK TO COVER 2. OK 3 - 4" CONDUITS FROM SW GEAR AREA TO PANELS 3. OK 2 GROUND RODS 6' PLUS APART 3/0 COPPER NOTE ON SWITCH GEAR - DUE TO AGE AND PREVIOUS USE INSPECTOR IS REQUESTING RECERTIFICATION BY TESTING LAB PRIOR TO RELEASE. |