Permit: T06CM06428

Parcel: 14111031A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXITS NOT WORKING PROPERLY
2. QUARTZ RESTROKE ON HIBAY FIXTURE NOT WORKING
3. CANNOT USE SHEETMETAL SCREW FOR GROUND CONNECTION @ ROOFTOP UNIT DISCONNECT.
4. VERIFY THAT GROUND WIRE TO A/C UNIT IS #10
5. LIGHT FIXTURE 2X4 AT FRONT DOOR TO HAVE BATTERY BACKUP. SEE LEGEND SHEET E-2
03/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL NEUTRAL KIT AT SERVICE DISCONNECT
2. INSTALL BONDING JUMPERS AT BOND BUSHINGS
3. NEED CLEAR WORK AREA AT SERVICE DISCONNECT
4. INSTALL GROUNDING ELECTRODE CONDUCTOR AT TRANSFORMER.
5. BOND WATER PIPE, SPRINKLER PIPE, BUILDING STEEL TO SERVICE PER NEC 250.104 & 250.52

RECALL FOR SERVICE WHEN READY