Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXITS NOT WORKING PROPERLY 2. QUARTZ RESTROKE ON HIBAY FIXTURE NOT WORKING 3. CANNOT USE SHEETMETAL SCREW FOR GROUND CONNECTION @ ROOFTOP UNIT DISCONNECT. 4. VERIFY THAT GROUND WIRE TO A/C UNIT IS #10 5. LIGHT FIXTURE 2X4 AT FRONT DOOR TO HAVE BATTERY BACKUP. SEE LEGEND SHEET E-2 |
|
| 03/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL NEUTRAL KIT AT SERVICE DISCONNECT 2. INSTALL BONDING JUMPERS AT BOND BUSHINGS 3. NEED CLEAR WORK AREA AT SERVICE DISCONNECT 4. INSTALL GROUNDING ELECTRODE CONDUCTOR AT TRANSFORMER. 5. BOND WATER PIPE, SPRINKLER PIPE, BUILDING STEEL TO SERVICE PER NEC 250.104 & 250.52 RECALL FOR SERVICE WHEN READY |