Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2007 | ELECTRIC - FINAL | Approved | ||
| 07/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. STORE NOT TO BE OCCUPIED OR STOCKED BEFORE APPROVAL OF BUILDING OFFICIAL 2. PROPERLY IDENTIFY PANEL DIRECTORY -- NEC 408.4 3. GROUNDING ELECTRODE CONDUCTOR NOT MADE UP RIGHT IN TRANSFORMER -- NEC 250.30 A1 4. FINISH FIRE ALARM 5. CHECK CEILING FAN 6. CLEAN UP CEILING AREA & PROTECT MC BY ACCESS -- NEC 330.23 PROTECT - RE-ROUTE G.E.C 250.64B |