Permit: T06CM06425

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/05/2007 ELECTRIC - FINAL Approved
07/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. STORE NOT TO BE OCCUPIED OR STOCKED BEFORE APPROVAL OF BUILDING OFFICIAL
2. PROPERLY IDENTIFY PANEL DIRECTORY -- NEC 408.4
3. GROUNDING ELECTRODE CONDUCTOR NOT MADE UP RIGHT
IN TRANSFORMER -- NEC 250.30 A1
4. FINISH FIRE ALARM
5. CHECK CEILING FAN
6. CLEAN UP CEILING AREA & PROTECT MC
BY ACCESS -- NEC 330.23
PROTECT - RE-ROUTE G.E.C 250.64B