Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/07/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PAINT ALL EXPOSED PVC W/LATEX PAINT. BLOCK & CLAMP PVC EVERY 4' - INSTALL RAIN GUTTERS 2. SECURE ELEC. CONDUITS ON ROOF 3. MARK UNIT DATA PLATE FOR HEAT STRIP 4. PERMANENTLY I.D A/C UNITS 5. EXTEND ANY SEWER VENTS WITHIN 10' OF A FRESH AIR INTAKE 2' ABOVE INTAKE OPENING. 6. PROVIDE AIR BALANCE REPORT |