Permit: T06CM06418

Parcel: 115071290


Addresses:

1609 N STONE AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/12/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
PLUMBING FINAL OK
OK FOR C OF O S.T.O.I
06/07/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CORRECT DRAINAGE FITTINGS & COUPLINGS FOR 3-COMP SINK WITH CORRECT FLOW CONTROL & VENT FITTINGS

NOTE: SANITIZE INDIRECT DRAIN WILL BE REQUIRED TO BE 6" ABOVE FLOOR LEVEL BY HEALTH DEPT.

2. ALL INDIRECT DRAINS SHALL HAVE 1" AIR GAP
3. MAKE ALL FIXTURES WATER TIGHT
4. (2) SINKS DRAINAGE SHALL ONLY HAVE (1) SUP JOINT CONNECTION DOWNSTREAM OF J-BOND CONNECTION
5. PROVIDE VACUUM BREAKERS ON ALL HOSE BIBS
6. WATER HEATER TO BE INSTALLED PER DETAIL 204 PAGE P-3 AND HAVE PIPING PROPERLY INSULATED WITH EXPANSION TANK SECURED.
7. SECURE TEMPERING VALVES AT ALL LAV'S