Permit: T06CM06418

Parcel: 115071290


Addresses:

1609 N STONE AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
04/03/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
1. ABS DWV UNDERSLAB OK TO COVER
WATER TEST THRU ROOF OK
04/02/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
SERVICE BASIN NOT INSTALLED PER PLAN
STAND PIPE CLEANOUT
HORIZ X HORIZ CHANGE OF ELEVATION TO BE A SWEEP
RISER FOR P-6 CUT OFF BELOW FLOOR
GREASE TRAP FLOW CONTROL NOT APPROVED
G.W STUB TOO HIGH
NO FLOW CONTROL VENT
OK TO COVER YARDWATER
03/16/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. ADD 03040 YARDWATER TO PERMIT AND CALL YARDWATER INSPECTIONS USING THIS CODE.
2. REQUIRE THREE FEET HORIZONTAL EACH SIDE OF RPPBP TO BE TYPE "L" COPPER. SAME AT SERVICE.
3. REQUIRE MINIMUM 12" COVER AT ALL POINTS FOR YARDWATER. REMOVE DEBRIS AND ROCKS.
4. ROUGH SOIL NOT INSTALLED PER PLAN
NO REDLINES ON SITE
NOT INSTALLED TO CODE
NO TEST
PLUMBER TO BE ON SITE AT TIME OF NEXT INSPECTION PLEASE HAVE A COPY OF YOUR LICENSE.