Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL ROOFTOP GFI SERVICE RECEPTACLE 2. MARK ACCESSORIES INSTALLED IN ROOFTOP A/C UNITS, IF NONE MARK NONE 3. CANNOT READ FUSE SIZE ON EXISTING UNITS/REPLACE FUSES WITH NEW 4. REMOVE OLD SERVICE FROM BUILDING 5. HOW WATER RECIRC PUMP MARKED FOR INDOOR USE ONLY 6. PROVIDE LISTING OF WATER HEATER TO BE USED OUTDOORS -- PLAN A-2 CALLS FOR WATER HEATER ENCLOSURE BY SPACEMAKER OR EQUAL. 7. STRAP/SECURE LIQUID TIGHT ON ROOF PER NEC 356.30 8. TIGHTEN ALL CONNECTORS ON LIQUID TIGHT FOR ROOFTOP UNITS. |
|
| 05/22/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/17/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ABOVE CEILING INSPECTION ONLY -- 1. HAVE OVERFILLED J-BOXES -- NEC 314.16 2. ROMEX STAPLES INTO DRYWALL NOT EFFECTIVE FOR SECURING MC -- NEED TO GO INTO FRAMING OR USE ANCHORS NEC 330.30 3. ALL COVERS TO BE CLOSED FOR INSPECTION 4. INSTALL SUPPORT WIRES FOR ALL LIGHT FIXTURES (OPPOSITE CORNERS) 5. SUPPORT ALL WIRING OFF CEILING GRID 6. MC TO BE SECURED WITHIN 12" OF TERMINATIONS - NEC 330.30 7. EQUIPMENT GROUNDS #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH -- NEC 250.119 8. WRAP GROUND AROUND & TIGHTEN J-BOX GROUND SCREWS NEC 110 9. CLOSE OFF SPARE RACEWAYS ABOVE PANEL -- NEC 110 SERVICE HAS NOT BEEN INSPECTED -- NOT TO BE ENERGIZED |