Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/01/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL TESTED DUCT SMOKE DETECTOR |
|
| 08/15/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PAINT ALL EXPOSED PVC W/LATEX PAINT EXTEND 1 SEWER VENT 2' ABOVE FRESH AIR INTAKE INCLUDE NEW CONDENSOR AND COOLER TO PLANS NEED TO TEST DUCT SMOKE DETECTOR PROVIDE AIR BALANCE REPORT |