Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM06413
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 04/23/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* | |
| 04/12/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NEED TRUSS REPAIR FOR ENTRY TRUSSES |
|
| 03/29/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) AT ENTRY TOWER, WRONG TRUSSES INSTALLED CHECK PITCH COMPARED TO OTHER TRUSSES 2) REMOVE RED BEARING TAGS AT AB2 3 PT THEY ARE 2 PT ONLY 3) WIND BRACE WEST WALL OF TOWER 4) MISSED NAILING ON ROOF (MARKED IN BLACK) 5) MISSED SHEARWALL BLOCKING AT EAST REAR PORTION OF WALL FROM WINDOW TO BACKWALL 6) CONNECT SHEAR GARAGE PER 17/D1 |