Permit: T06CM06411

Parcel: 10602265B


Addresses:

320 W PRINCE RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/12/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/25/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
TALKED ABOUT TRANSFORMER THAT WILL SUPPLY POWER FOR X-RAY EQUIPMENT - I DO NOT CONSIDER THIS TRANSFORMER AS PART OF X-RAY AS OUTLINED IN NEC 517.76 SECONDARY WILL NEED OVERCURRENT PROTECTION PER
NEC 240.21
06/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO ENERGIZE PANEL "P3" LOCKOUT OPEN WIRING
OK TO COVER WALLS IN X-RAY ROOM

NOTE: STILL NEED THE APPROVED PLANS X-RAY ROOM
04/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR WALL COVER - NO HARD LIDS APPROVED BOXES ON TOP PLATES TO BE PROPERLY MOUNTED BEFORE CEILING COVER.
04/23/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL ALL MUD RINGS
2. INSTALL MC NAIL PLATES AS NEEDED (AND) PVC
3. INSTALL GROUNDING MEANS FOR ALL BOXES
4. BOXES NOT PROPERLY MOUNTED
5. PAINT EXTERIOR OF BOXES CONTAINING FIRE ALARM TERMINATIONS
6. SEAL FLEX FOR TEMP FEEDER SO WATER CAN'T ENTER
7. GROUNDING ELECTRODE CONDUCTOR RACEWAY TO BE ELECTRICALLY CONTINUOUS OR NON-FERROUS
04/18/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. GROUNDING ELECTRODE CONDUCTOR IN METAL RACEWAY TO BE ELECTRICALLY CONTINUOUS -- NEC 250.64(E)
INTERIOR NOT READY