Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/25/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* TALKED ABOUT TRANSFORMER THAT WILL SUPPLY POWER FOR X-RAY EQUIPMENT - I DO NOT CONSIDER THIS TRANSFORMER AS PART OF X-RAY AS OUTLINED IN NEC 517.76 SECONDARY WILL NEED OVERCURRENT PROTECTION PER NEC 240.21 |
|
| 06/19/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO ENERGIZE PANEL "P3" LOCKOUT OPEN WIRING OK TO COVER WALLS IN X-RAY ROOM NOTE: STILL NEED THE APPROVED PLANS X-RAY ROOM |
|
| 04/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR WALL COVER - NO HARD LIDS APPROVED BOXES ON TOP PLATES TO BE PROPERLY MOUNTED BEFORE CEILING COVER. |
|
| 04/23/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL ALL MUD RINGS 2. INSTALL MC NAIL PLATES AS NEEDED (AND) PVC 3. INSTALL GROUNDING MEANS FOR ALL BOXES 4. BOXES NOT PROPERLY MOUNTED 5. PAINT EXTERIOR OF BOXES CONTAINING FIRE ALARM TERMINATIONS 6. SEAL FLEX FOR TEMP FEEDER SO WATER CAN'T ENTER 7. GROUNDING ELECTRODE CONDUCTOR RACEWAY TO BE ELECTRICALLY CONTINUOUS OR NON-FERROUS |
|
| 04/18/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. GROUNDING ELECTRODE CONDUCTOR IN METAL RACEWAY TO BE ELECTRICALLY CONTINUOUS -- NEC 250.64(E) INTERIOR NOT READY |