Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM06402

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/03/2008 BUILDING - FINAL Approved IVRS - Inspection :*
05/01/2008 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) PENDING FIREPLACE LOGS
04/23/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/04/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED POST TENSION TAG ON WATER LINE
2) 2 RECEPTACLES AT GARAGE A/C
3) INSTALL FLOOR RECEPTS
4) NO EXPOSED LAMP IN CLOSETS
5) MASTER BATH RECEPTS INOPERABLE
6) LAUNDRY RECEPT WONT RESET
7) OPEN NEUTRAL ISLAND
8) NEED DRIP LEG ON FURNACE
9) INSTALL VALVE BEFORE FLEX
10) NEED GAS VALVES FOR FIREPLACES
11) SEAL GAS SLEEVE IN ISLAND
12) A/C FUSES 40 AMPS
13) RAISE CONDENSATE VENT ABOVE DRAIN HEIGHT
14) INSTALL SECONDARY CONDENSATE DRAIN OR SHUT OFF SWITCH