Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06395
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WORK COVERED W/O INSPECTION 2. PLAN DOES NOT COINCIDE WITH WORK 3. PNL B-1 ON PLAN IS B-3 ON SITE AND CIRCUITRY DOES NOT MATCH WITH PLAN. 4. PNRP ON PLAN IS 100 A - ON SITE 30 AMP TOO MANY CIRCUITS ON RP WHICH IS ONLY 30A APPROX 26 CIRCUITS PLAN APPROVED IS OFFICE GENERIC, NOT WHAT IS JOB INSTALLED. |
|
02/22/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ON JOB SITE 1:15 PM NO CONTRACTOR ON SITE NO ANSWER FROM # ABOVE, NO PLANS, NO MESSAGE |