Permit: T06CM06374

Parcel: 141315870

Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T06CM06374

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2007 ROOF NAILING Approved IVRS - Inspection :*
04/02/2007 ROOF NAILING Partial Approval IVRS - Inspection :*
1) #13 NAIL THA HANGERS TRUSS TO GIRDER ROOF
2) REPAIR SHEAR TRANSFER LIVING ROOM PER REVISED DETAIL
3) MISSED PHAD42 AT REAR SLIDER
5) #5 SHEAR LIVING ROOM NAIL ALL HORIZONTAL JOINTS, OSB IS COVERED
03/28/2007 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FROM LAST INSPECTION FIX FOR NOTCHED GABLE TRUSSES CLOSER THAN 24" TO HEEL JNT
2) NAIL ALL VERTICAL STUDS ATTACHED TO P.A. STRAPS AND FUTURE H.D.'S
3) WEST WALL MISSING NAILING SHEAR AT CORNER OF LIVING ROOM
4) #7 SHEAR 3" EDGE NAILING
5) FRONT 2ND FLOOR CMST STRAP TO GO ON END OF SHEARWALL
6) NAIL ALL WIND BRACES
7) #5 SHEAR 10/DT1 16" ON CENTER A.35 F
8) BUILT UP TO TOP PLATES FRONT PORCH, NOT TIED TO BEAMS
9) WRONG SIZE NAILS REAR P.A., MISSED P.A. AT REAR WALL
10) #8 SHEAR FRONT WALL 3" EDGE NAILING
11) BLOCK OSB FRONT PORCH TURNED WRING WAY
12) SUPPORT FOR FRONT POP OUT 2ND FLOOR AT BOTTOM PLATE
13) NAIL ? HANGERS 2ND FLOOR
14) NEED DETAIL SHEAR TRANSFER LIVING ROOM WEST WALL
15) 48" ON CENTER 1ST TO 2ND FLOOR STRAPS (REAR, FRONT AND SIDES)
03/22/2007 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NAIL ALL VERTICAL STUDS AT EACH H.D.
2) #7 SHEARWALL AT FAMILY ROOM 3"-12" ON CENTER
3) NAIL ALL WIND BRACES
4) USE 10/DT1 TO TIE SHEARWALLS TO TRUSS CHORD
5) FINISH BOLTING ALL HD8A H.D.'S
6) 3/DT2-REVISION SEE NEW DETAIL
7) THA HANGERS ROOF BEND STRAPS OVER BEAM & NAIL
8) AT FRONT PORCH TIE DBL 2 X 4 PLATES TO BEAM
9) #9 SHEAR GARAGE TO HOUSE NAIL A 2"-12"
10) MISSED NAILING GARAGE ROOF
11) CHECK SHEAR NAILING ON ALL HORIZONTAL AND VERTICAL JOINTS REAR WALL 1ST AND 2ND FLOOR
12) NO NOTCHING TOP CHORD OF GABLE TRUSSES 24" FROM HEEL JOINT
03/19/2007 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO LADDER ACCESS TO ROOF
03/16/2007 ROOF NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO PLANS/PERMITS
2) FRAMING CREW STILL WORKING ON HOUSE