Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/11/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. VENT ON CONDENSATE TRAP MUST BE DOWNSTREAM OF TRAP 2. SUPPORT DUCT AT FLEX CONNECTOR 3. REMOVE STRAPS FROM FLEX CONNECTORS 4. LABEL FAN COILS AND CONDENSORS 5. TIGHTEN LOOSE ELEC. FITTINGS ON CONDENSORS 6. PROVIDE A GFI SERVICE RECEPTACLE AT CONDENSORS |