Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/12/2008 | MECHANICAL - INTERMEDIATE | Approved | ||
| 06/25/2008 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL ALL DUCT PER PLANS 2. REMOVE STRAP FROM FLEX CONNECTOR 3. FLEX NOT CONNECTED PER PLANS 4. BRANCH TAPS NOT PER DETAIL 105 5. PROVIDE SPRING ISOLATORS PER DETAIL 101 NOTE: PLANS REQUIRE OUTSIDE AIR BUT NO DUCTING SHOWN ON PLANS REFER TO ENGINEER FOR CORRECTIONS. |