Permit: T06CM06362

Parcel: 13608477H

Inspection Status: Approved

Inspection History: ELECTRIC - OUTDOOR LIGHTING

Date Description Inspector Results Comments
09/16/2008 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
09/12/2008 ELECTRIC - OUTDOOR LIGHTING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL ALL MOUNTING HARDWARE FOR RECEPT IN INDUSTRIAL COVERS
2. STRAP MC WITHIN 12" OF BOX
3. INSTALL MISSING WALL PLATE
4. NEED DISCONNECTING MEANS FOR INSTANT HOT
5. NUMBER BREAKERS IN PANEL
6. EM LIGHTING TO TIE INTO LIGHTING CIRCUIT IN AREA
7. AIM EM LIGHTING TO BE EFFECTIVE
8. INSTALL BONDING SCREW AT AC DISCONNECT
9. INSTALL PROPER OVERCURRENT PROTECTION FOR
INSTANT HOT
10. STRAP CABLE FOR INSTANT HOT
11. IS BUILDING STEEL AND WATER BONDED TO SERVICE?
12. OPEN PANELS FOR INSPECTION
09/05/2008 ELECTRIC - OUTDOOR LIGHTING Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR