Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2008 | ELECTRIC - CABLE DROP | Approved | ||
| 07/01/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 06/27/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED ACCESS PANEL FOR LB 2. INSTALL GEC TO NEUTRAL. DO NOT USE GEC AS BONDING JUMPERS. INSTALL BONDING JUMPERS TO PREVENT OBJECTIONABLE CURRENT FLOW 3. MARK "SERVICE DISCONNECT" 4. INSTALL FUSES 5. OK U.G FROM SES TO TEP XFMR. INSTALL WARNING RIBBON NEC 300.5 6. TERMINATE LINE AND LOAD PROPERLY IN METER & DISCONNECT |
|
| 06/25/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. NEED TO POST BOND TO GET POWER RELEASED 2. CONTRACTOR STILL WORKING ON SERVICE |