Permit: T06CM06362

Parcel: 13608477H

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
09/16/2008 ELECTRIC - CABLE DROP Approved
07/01/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
06/27/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED ACCESS PANEL FOR LB
2. INSTALL GEC TO NEUTRAL. DO NOT USE GEC AS BONDING JUMPERS. INSTALL BONDING JUMPERS TO PREVENT OBJECTIONABLE CURRENT FLOW
3. MARK "SERVICE DISCONNECT"
4. INSTALL FUSES
5. OK U.G FROM SES TO TEP XFMR. INSTALL WARNING RIBBON NEC 300.5
6. TERMINATE LINE AND LOAD PROPERLY IN METER & DISCONNECT
06/25/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. NEED TO POST BOND TO GET POWER RELEASED
2. CONTRACTOR STILL WORKING ON SERVICE