Permit: T06CM06355

Parcel: 13728078A


Addresses:

949 W HAWAII DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
06/19/2007 BUILDING - FINAL Approved IVRS - Inspection :*
06/14/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MASTER BEDROOM RECEPTACLE ON EAST BLOCK WALL HAS AN OPEN NEUTRAL (MAYBE WORN RECEPTACLE)
3) BREAK AWAY BAR IN S. BEDROOM, HINGE IS NEXT TO OUTSIDE FLOOD LIGHT OBSTRUCTS FULL OPENING
06/05/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REVERSED POLARITY ON RECEPTACLE BY SINK
2) INSTALL SMOKE DETECTORS IN BEDROOMS AND HALLWAYS LEADING TO BEDROOMS
3) DRAFT STOP AROUND WATER HEATER FLUE
4) NO POWER TO SWITCHED RECEPTACLE IN M. BEDROOM
5) PROVIDE FUNCTIONING BREAK AWAY BARS IN BEDROOMS
6) SERVICE PANEL JAMED SHUT
02/20/2007 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*