Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 06/14/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MASTER BEDROOM RECEPTACLE ON EAST BLOCK WALL HAS AN OPEN NEUTRAL (MAYBE WORN RECEPTACLE) 3) BREAK AWAY BAR IN S. BEDROOM, HINGE IS NEXT TO OUTSIDE FLOOD LIGHT OBSTRUCTS FULL OPENING |
|
| 06/05/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVERSED POLARITY ON RECEPTACLE BY SINK 2) INSTALL SMOKE DETECTORS IN BEDROOMS AND HALLWAYS LEADING TO BEDROOMS 3) DRAFT STOP AROUND WATER HEATER FLUE 4) NO POWER TO SWITCHED RECEPTACLE IN M. BEDROOM 5) PROVIDE FUNCTIONING BREAK AWAY BARS IN BEDROOMS 6) SERVICE PANEL JAMED SHUT |
|
| 02/20/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |