Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM06353
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2007 | MECHANICAL - FINAL | Approved | ||
06/27/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PROVIDE THE PROPER ENCLOSURE FOR THE CONDENSOR ON ROOF. - PROVIDE PROPER FUSING. - PROVIDE PERMANENT DATA INSIDE EQUIPMENT - PROVIDE AIR BALANCE REPORT - OK TO FILE FOR TEMP C OF O |
|
06/26/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* TYPE I EXHAUST NOT EXTENDED HIGH ENOUGH EXTEND DUCT ALL ONE PIECE FROM DUCT BELOW EXTEND ROOF CURB & PROVIDE A WAY TO CLEAN DUCT DO NOT WELD FAN TO DUCT CHECKED DUCT SMOKE DETECTORS PROVIDE AIR BALANCE REPORT |
|
06/21/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE AUDIBLE & VISIBLE ALARMS ON DUCT SMOKE DETECTORS. DETECTORS NOT SHUTTING OFF A/C FANS. 2. MAKE UP AIR OVERFUSED. USE PROPER COLOR WIRES. NO WHITE. 3. CANNOT IDENTIFY FUSES FOR A/C 4 4. PROVIDE A COVER OVER CONDENSOR 5. TYPE 1 EXHAUST TO EXTEND TO TOP OF PARAPET. PROVIDE GREASE CUP. 6. PERMANENTLY I.D UNITS. PROVIDE AIR BALANCE REPORT. LEFT GAS CARD. |