Permit: T06CM06353

Parcel: 136261290

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/29/2007 MECHANICAL - FINAL Approved
06/27/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- PROVIDE THE PROPER ENCLOSURE FOR THE CONDENSOR
ON ROOF.
- PROVIDE PROPER FUSING.
- PROVIDE PERMANENT DATA INSIDE EQUIPMENT
- PROVIDE AIR BALANCE REPORT
- OK TO FILE FOR TEMP C OF O
06/26/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
TYPE I EXHAUST NOT EXTENDED HIGH ENOUGH
EXTEND DUCT ALL ONE PIECE FROM DUCT BELOW
EXTEND ROOF CURB & PROVIDE A WAY TO CLEAN DUCT
DO NOT WELD FAN TO DUCT
CHECKED DUCT SMOKE DETECTORS
PROVIDE AIR BALANCE REPORT
06/21/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE AUDIBLE & VISIBLE ALARMS ON DUCT SMOKE DETECTORS. DETECTORS NOT SHUTTING OFF A/C FANS.
2. MAKE UP AIR OVERFUSED. USE PROPER COLOR WIRES.
NO WHITE.
3. CANNOT IDENTIFY FUSES FOR A/C 4
4. PROVIDE A COVER OVER CONDENSOR
5. TYPE 1 EXHAUST TO EXTEND TO TOP OF PARAPET. PROVIDE GREASE CUP.
6. PERMANENTLY I.D UNITS. PROVIDE AIR BALANCE REPORT. LEFT GAS CARD.