Permit: T06CM06353

Parcel: 136261290

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06353

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
06/26/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- RECEIVED (6) IN HOUSE BACKFLOW CERTIFICATIONS
- RECEIVED CLEAN BACTERIA REPORT FOR POTABLE
WATER SYSTEM.

1. MENS RESTROOM STOOL TO HAVE FLUSH HANDLE TO WIDE SIDE OF ROOM.
06/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE CORRECT BACKFLOW PROTECTION WITH CERTIFICATION FOR SODA DISPENSERS & AGUAS FRESCAS DISPENSER.
2. SHALL LATEX PAINT VENT FROM DWV THRU ROOF
3. PROVIDE LISTING PLATES FOR ALL GAS APPLIANCES AT COOKING BATTERY.
4. INDIRECT DRAINS TO HAVE 1" AIR GAP
5. TERMINATE DRAIN FROM AGUAS FRESCAS DISPENSER PROPERLY
6. ICEMAKER TO BE INSTALLED PROPERLY
7. COMPLETE INSTALLATION OF INSULATION ON
HOT & RETURN PIPING