Permit: T06CM06353

Parcel: 136261290

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06353

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
OK FOR TEMP C OF O
06/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CONDENSING UNIT FOR WALK IN HAS ALL LABELING & NAME PLATE DATA PAINTED OVER. HAS HOMEMADE COVER INSTALLED UNIT DOES NOT APPEAR TO BE OUTDOOR UNIT.
CANNOT VERIFY REQUIRED CIRCUIT SIZE OR OVERCURRENT REQUIREMENTS. CONNECTIONS TO UNIT ARE LOOSE & NEED TO BE TIGHTENED.
2. ALL OTHER PREVIOUS ITEMS CORRECTED
06/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL DISCONNECT FOR FAN COIL UNIT IN WALK IN
2. SEAL ALL RACEWAYS ENTERING WALK IN -- NEC 300.7
3. INSTALL BOX EXTENSIONS WHERE REQUIRED
4. INSTALL DISCONNECT ON INSTA-HOT 422.30 & 422.31
5. ALL 15 & 20 AMP 125V RECEPTACLES IN KITCHENS TO BE GFI
6. INSTALL PROPER SIZE GROUND TO A/C UNITS 250.122
7. CANNOT USE WHITE WIRE AS PHASE CONDUCTORS
NEC 200.6, 200.7, 300.12
8. INSTALL FLEX TO EXHAUST FAN PER MANUFACTURES INSTRUCTIONS -- NEC 110.3
9. CONDENSING UNIT FOR WALK IN COOLER HAS ALL MARKING LABELS PAINTED OVER & APPEARS TO BE INDOOR UNIT ONLY
WILL NOT ACCEPT UNIT IN CONDITION IT IS IN. PROVIDE INSTALLATION INSTRUCTIONS & LISTING OF UNIT -- NEC 110.3