Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 05/15/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PERMANENTLY I.D ALL EQUIPMENT ON ROOF WITH SUITE NUMBER & EQUIPMENT NAME OR NUMBER (WALK IN COOLER, WALK IN FREEZER, AC-1, AC-2, ETC. 2. MARK AC UNIT IN DATA PLATE W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 3. PROVIDE A FRESH AIR INTAKE 4. PROVIDE AN AIR BALANCE REPORT 5. CLEAN THE TAR OUT OF THE VENT ON CONDENSATE TRAP. VENT MUST BE DOWNSTREAM OF THE TRAP. TESTED DUCT SMOKE DETECTORS. |