Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM06349
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* RECEIVED COPY OF (3) BACKFLOW CERTIFICATIONS FOR IN HOUSE DEVICE BY RICHARD GRAVES #C569 |
|
05/15/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SEE NOTE #2 PROVIDE FULL SIZE DRAIN WITH APPROVED DRAINAGE MATERIAL. 2. SEE NOTE #3 BACKFLOW DEVICE TO BE MOUNTED NO HIGHER THAN 5' FROM FINISH FLOOR. 3. PROVIDE LISTING FOR 3/8 WATER TUBING USED OR PROVIDE APPROVED MATERIAL FOR WATER SUPPLIES TO MACHINES. 4. SEE NOTE #6 AND COMPLY 5. SEE NOTE #8 AND COMPLY 6. ALL INDIRECT DRAINS TO BE PROPERLY SUPPORTED. |
|
05/11/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SHALL PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR SINK DRAINS. TO AN APPROVED RECEPTOR 2) SHALL PROVIDE SEPERATE DRAINS FOR ICE MACHINE BIN AND MAKER DRAINS 3) SHALL PROVIDE PROOF OF 1" AIR GAP, LISTING FOR BACKFLOW PROTECTION, OR CORRECT BACKFLOW DEVICE FOR ICE MACHINE 4) ITEM #3 ABOVE ALSO APPLIES TO (2) SEPERATE JUICE MACHINES 5) INDIRECT DRAINS OVER 5' IN LENGTH SHALL BE DIRECTLY TRAPPED 6) PROVIDE CORRECT DRAINAGE FOR 2 COMPARTMENTS OF 3 COMP SINK 7) MAKE WATER TIGHT ALL FIXTURES 8) PUBLIC USE LAVS REQUIRE SEPERATE MEANS TO CONTROL HOT WATER TEMPERATURE BESIDES WATER HEATER CONTROL. NOT READY 9) TESTABLE DBL CHECK VALVE ASSEMBLY |