Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM06349

Parcel: 13348128F

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06349

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/15/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL WEATHERPROOF COVERS ON DEVICES IN WALK INS
2. INSTALL EMERGENCY LIGHT FIXTURE IN BACK ROOM PER PLAN
3. ATTACH GROUND WIRE TO DISCONNECT FOR REFRIGERATION EQUIPMENT
4. INSTALL PROPER SIZE FUSES FOR CONDENSING UNITS ON ROOF
5. CAP OPEN SPARE 3/4" EMT AT PANEL