Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06349
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/15/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. INSTALL WEATHERPROOF COVERS ON DEVICES IN WALK INS 2. INSTALL EMERGENCY LIGHT FIXTURE IN BACK ROOM PER PLAN 3. ATTACH GROUND WIRE TO DISCONNECT FOR REFRIGERATION EQUIPMENT 4. INSTALL PROPER SIZE FUSES FOR CONDENSING UNITS ON ROOF 5. CAP OPEN SPARE 3/4" EMT AT PANEL |