Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/11/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL TIE WIRES ON RECESSED FIXTURES 2) SUPPORT TRACK LIGHTS INDEPENDENT OF GROUND 3) SUPPORT MC CABLES EVERY 6' AND WITHIN 12" OF BOXES 4) OVERFILL ON JUNCTION BOXES 5) SEAL ALL OPEN KNOCKOUTS IN JUNCTION BOXES 6) INSTALL PENDANT FIXTURE 7) RECESSED FIXTURES INSTALLED DO NOT MATCH WHAT PLAN IS CALLING FOR. CHECK LOAD ON BRANCH CIRCUIT |