Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM06349
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/11/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL TIE WIRES ON RECESSED FIXTURES 2) SUPPORT TRACK LIGHTS INDEPENDENT OF GROUND 3) SUPPORT MC CABLES EVERY 6' AND WITHIN 12" OF BOXES 4) OVERFILL ON JUNCTION BOXES 5) SEAL ALL OPEN KNOCKOUTS IN JUNCTION BOXES 6) INSTALL PENDANT FIXTURE 7) RECESSED FIXTURES INSTALLED DO NOT MATCH WHAT PLAN IS CALLING FOR. CHECK LOAD ON BRANCH CIRCUIT |