Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM06349

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
05/11/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL TIE WIRES ON RECESSED FIXTURES
2) SUPPORT TRACK LIGHTS INDEPENDENT OF GROUND
3) SUPPORT MC CABLES EVERY 6' AND WITHIN 12" OF BOXES
4) OVERFILL ON JUNCTION BOXES
5) SEAL ALL OPEN KNOCKOUTS IN JUNCTION BOXES
6) INSTALL PENDANT FIXTURE
7) RECESSED FIXTURES INSTALLED DO NOT MATCH WHAT PLAN IS CALLING FOR. CHECK LOAD ON BRANCH CIRCUIT