Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* 1) REPLACE 40 AMP CB'S ON #10 WIRE WITH 30 AMP CB'S |
|
| 09/11/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE A LISTED MAST BRACE 2. CONNECT UFER TO SERVICE 3. GROUND RODS TO BE 6' MINIMUM APART 4. POWER WILL NOT BE APPROVED BEFORE UNITS ARE TRIMMED OUT OR GFI UNDER SERVICE FOR TEMP POWER 5. NEED TO APPLY FOR OVERHEAD SERVICE WAIVER |
|
| 08/28/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* NEED ADDRESS AND UNIT #'S TO SHOW 1 OR 2 |