Permit: T06CM06348

Parcel: 10605020E


Addresses:

420 W PELAAR DR #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/28/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
REINSTALL WIRING AT SECTION REMOVED
TO GET SHOWER OUT
08/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
UNIT #1
1. RECESSED LIGHT WASHER ROOM NEEDS COVER
2. THE SUB-PANEL MUST HAVE THE NEUTRALS & GROUNDS ISOLATED, THE BAR BEHIND CONNECTS THEM BOTH
3. THE SMALL BAR SHOULD CONNECT THE GROUND WIRES TO CASE NOT NEUTRAL

UNIT #2
1. RECESSED LIGHT IN KIT. MISSING COVER
2. SAME AS #1
3. SAME AS #1