Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 02/27/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 3" VENT AND 4" GREASE WASTE FROM INTERCEPTOR VENT TO 10' AFF GREASE WASTE TO 3' DOWNSTREAM OF INTERCEPTOR OK 2 1/2 WATER SERVICE STUB UP & OUT 4' AIR TEST OK |
|
| 02/26/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* - 4" GREASE WASTE INTO INTERCEPTOR THRU INTERCEPTOR OK - SHALL INSTALL VENT FOR INTERCEPTOR PER PLAN. |
|
| 02/22/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST 4" GREASE WASTE TO 2' FROM INTERCEPTOR OK 4" SANITARY FROM 3' EXTERIOR THRU BUILDING UNDERGROUND WATER TEST OK 1. SHALL SEE CONTINUATION OF BOTH SYSTEMS TO EXISTING SEWER, SHALL HAVE APPROVED SITE PLAN. |