Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06338
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL CIRCUITS IN PANEL AT MANAGERS OFFICE 2. INSTALL EXTENSIONS ON SWITCH BOXES IN BATHROOMS. BOXES BACK MORE THAN 1/4" 3. INSTALL FILLER PLATE IN DEAD FRONT OF PANEL B 4. LABEL DISCONNECT SWITCHES IN WATER HEATER CLOSET 5. MISSING SWITCH PLATE IN WATER HEATER CLOSET. 6. SOME OUTDOOR LIGHTS NOT WORKING/MISSING LAMPS 7. CANNOT USE SHEETMETAL SCREW FOR GROUND CONNECTIONS IN ROOF DISCONNECTS 8. ONE GROUND PER LUG IN DISCONNECTS 9. PROVIDE LADDER TO INSPECT UNITS ON ROOF |