Permit: T06CM06338

Parcel: 136406760


Addresses:

9530 E 22ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06338

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/06/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LABEL CIRCUITS IN PANEL AT MANAGERS OFFICE
2. INSTALL EXTENSIONS ON SWITCH BOXES IN BATHROOMS.
BOXES BACK MORE THAN 1/4"
3. INSTALL FILLER PLATE IN DEAD FRONT OF PANEL B
4. LABEL DISCONNECT SWITCHES IN WATER HEATER CLOSET
5. MISSING SWITCH PLATE IN WATER HEATER CLOSET.
6. SOME OUTDOOR LIGHTS NOT WORKING/MISSING LAMPS
7. CANNOT USE SHEETMETAL SCREW FOR GROUND CONNECTIONS IN ROOF DISCONNECTS
8. ONE GROUND PER LUG IN DISCONNECTS
9. PROVIDE LADDER TO INSPECT UNITS ON ROOF