Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/06/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. INSTALL EXIT AT BACK DOOR 2. NEED TO INSPECT RELAY BOXES WHEN FINISHED 3. OK CEILINGS |
|
| 06/05/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED TO CHECK CONNECTION AT EMERGENCY EGRESS LIGHTING AT FRONT OF STORE, SIDE AND BACK ENTRANCES 2) GROUND ALL BOXES 3) INSTALL 12 GAUGE SEISMIC WIRES ON ALL LIGHTS IN DROP CEILING 4) RELAY BOX NOT UP AND BOTH BOXES NOT CLOSED 5) SECURE SEAL TIGHT AREA WALK IN COOLERS 6) MISSING EXIT FIXTURE AT BACL DOOR 7) RECEIVED LETTER OF TORQUE |
|
| 04/09/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |