Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06338
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PICKED UP MC LETTER 2) OK BATHROOM CEILINGS ONLY 3) OK WATER, SPRINKLER, GAS AND BOND 4) #10 INSTALLED TO GROUND 30 OUTLET BOXES OK |
|
04/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEED TO BOND WTR PIPING GAS PIPING & SPRINKLER SYSTEM TO SERVICE 2. INSTALL #10 AWG GROUND WIRES TO 30A OUTLET BOXES 3. NEED LETTER FROM ENGINEER ALLOWING USE OF MC CABLE 4. OK WALLS |
|
03/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 3 SIGN CIRCUITS ON ROOF LEVEL |