Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM06338
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
07/03/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC CONDUITS TO POST COLUMNS FOR SIGNS @ DRIVE THRU |
|
05/14/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK 4" PVC FOR TELEPHONE 2. OK (2) 4" PVC FROM CORNER OF BUILDING TO SES (1) 90 DEG. ELBOW EACH RUN 3. INSTALL WARNING RIBBON PER NEC 300.5 |
|
05/09/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. OK (2) 4" PVC FROM CORNER OF BUILDING 20' FROM TEP TRANSFORMER OK (1) 90 DEG. ELBOW EACH RUN 2. INSTALL WARNING RIBBON PER NEC 300.5 |
|
02/28/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK PANEL FEEDER SES AREA TO STUB UP INSIDE BLDG 2) OK 20' COPPER UFER. SERVICE PVC RISER FOR TEMP SERVICE OK PER CARL VEREEN AT TEP |