Permit: T06CM06336

Parcel: 12607033D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM06336

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2010 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL
04/20/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE A DISCONNECT AT FAN COIL
PROVIDE SCREENS ON COMBUSTION AIR INTAKES
SECURE CONDENSOR TO SLEEPERS
PROVIDE AIR BALANCE REPORT
04/15/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. B-VENT MUST START BELOW CEILING
2. HIGH COMBUSTION AIR TO BE MAX. 12" FROM CEILING
3. AH-2 WASTE VENT TOO CLOSE TO O.S.A INLET
4. IDENTIFY ALL UNIT DATA PLATES (HEAT PUMPS)
5. PROVIDE AIR BALANCE REPORT