Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2010 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) OK FOR FINAL |
|
| 04/20/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE A DISCONNECT AT FAN COIL PROVIDE SCREENS ON COMBUSTION AIR INTAKES SECURE CONDENSOR TO SLEEPERS PROVIDE AIR BALANCE REPORT |
|