Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2008 | ELECTRIC - UFER | Approved | IVRS - Inspection :* NOTE: CLAMPS TO REBAR GENERALLY NEED TO BE USED AS THEY ARE LISTED TO BE USED AND PROPERLY TIGHTENED/INSTALLED. THIS UFER WAS APPROVED BASED ON THE 20' CONDUCTOR IN FOOTING AS THE ELECTRODE. IF THESE CLAMPS WOULD HAVE BEEN CONNECTED TO REBAR AS GROUNDING ELECTRODE, INSPECTION WOULD HAVE FAILED |
|
| 02/21/2008 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* |