Permit: T06CM06330

Parcel: 12607033C

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06330

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/14/2009 PLUMBING - FINAL Approved IVRS - Inspection :*
12/04/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
CAULK DFS
CORRECT DRIPS AT MV's
EXT. CO's NOT YET TRIMMED OUT
12/03/2008 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE VAC RELIEF VALVE AT WH PER UPC 608.7
2. LAVS REQUIRE MIXING VALVES
SEE PLAN SPEC. & CODE SEC. 414.1
3. PROVIDE WATER HAMMER ARRESTORS AT
FLUSH-O-METERS 609.10
4. CORRECT WATER HAMMER CONDITION AT WCS
5. CAULK DFS
6. TRIM OUT EXTERIOR CLEANOUTS