Permit: T06CM06327

Parcel: 12607033D

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM06327

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
1) SUBJECT TO BOND POSTING
2) ONLY AUTHORIZED PERSONS TO HAVE ACCESS TO ELECTRICAL EQUIPMENT
3) DO NOT ENERGIZE BLDGS OR UNITS PRIOR TO INSPECTORS APPROVAL
10/15/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1. SIZE BOND JUMPERS PER 250.66 FOR SUPPLY SIDE OF SERVICE
2. RECEIVED LETTER OF TORQUE
3. POST BOND FOR TEMP POWER
10/14/2008 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. PROVIDE ACCESS TO WATER BONDING
2. LETTER OF TORQUE
3. PROVIDE 1 LINE OR PLANS AT SERVICE EQUIP.
4. POST BOND FOR TEMP POWER FOR TEST