Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/28/2008 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 08/18/2008 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SIZE SERVICE BONDING AHEAD OF OVERCURRENT PER 250.66 NEC 3/0 CU 2. INSTALL BOND BUSHING OR BONDING LOCKNUTS PER 250.92 3. BOND BLD. STEEL 4. LABEL ALL DISCONNECTS 5. HAVE ENGINEER OF RECORD PROVIDE DETAILS OF GUTTER WIRING FOR FEEDERS NOT SHOWN ON PLAN |