Permit: T06CM06312

Parcel: 12710017D

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM06312

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
12/20/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
USE SWEEPS AT VERTICAL TO HORIZONTAL CHANGE OF DIRECTION.
INSTALL CLEANOUT
TEST ALL PIPING TO TIE IN POINT
NO FERNCO COUPLING USE MISSION BANDS
SEE PREVIOUS NOTES.
12/19/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BELOW GRADE BUILDING SEWER SHALL HAVE 12" OF COVER
2. TRACER WIRE IS REQUIRED OUTSIDE.
3. 10' HEAD TEST ON ALL DRAIN & VENT PIPING REQUIRED PROPER DRAINAGE FITTINGS REQUIRED
PIPING NOT SIZED PER PLAN
4. MINIMUM TRAP ARM DISTANCE IS 4"
5. VENT SHALL BE PROPERLY SUPPORTED AND SLOPED 6. WATER PIPING SHALL BE PROPERLY SUPPORTED
7. PROPER TRANSITION COUPLINGS AT C1 TO PL