Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
| 01/22/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE NAIL PLATES FOR MC AS NEEDED - NEC 330.17 2. PROVIDE BACK SUPPORT FOR BOXES TO KEEP THEM FROM ROLLING BACK INTO WALLS ON STEEL STUDS - NEC 314.23 OK TO COVER AFTER CORRECTIONS. |