Permit: T06CM06308

Parcel: 123090210


Addresses:

2919 E MABEL ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
12/27/2006 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
12/22/2006 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REMOVE ALL ABANDONED PIPE AT METER.
2. CONNECT ALL REMAINING GAS PIPE & PROVIDE
PRESSURE TEST.
3. SECURE 1/2" GAS LINE TO WALL FURNACE.
4. SECURE GAS LINE BEHIND CLOTHES DRYER.
5. PROVIDE A GAS SHUT OFF VALVE IN AN ACCESSIBLE LOCATION FOR WALL HEATER.
6. INCREASE VENT CONNECTOR TO 4" AT FURNACE OUTLET.
7. PROVIDE HOSE CLAMPS AT EACH END OF PLASTIC HOSE.
8. RELOCATE REFRIGERATION LINES FROM BLOCKING REMOVAL OF WATER HEATER.
9. PROVIDE FUSES IN DISCONNECT.
10. WHERE IS CONDENSATE TERMINATED? TERMINATE TO AN APPROVED LOCATION