Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/22/2006 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. REMOVE ALL ABANDONED PIPE AT METER. 2. CONNECT ALL REMAINING GAS PIPE & PROVIDE PRESSURE TEST. 3. SECURE 1/2" GAS LINE TO WALL FURNACE. 4. SECURE GAS LINE BEHIND CLOTHES DRYER. 5. PROVIDE A GAS SHUT OFF VALVE IN AN ACCESSIBLE LOCATION FOR WALL HEATER. 6. INCREASE VENT CONNECTOR TO 4" AT FURNACE OUTLET. 7. PROVIDE HOSE CLAMPS AT EACH END OF PLASTIC HOSE. 8. RELOCATE REFRIGERATION LINES FROM BLOCKING REMOVAL OF WATER HEATER. 9. PROVIDE FUSES IN DISCONNECT. 10. WHERE IS CONDENSATE TERMINATED? TERMINATE TO AN APPROVED LOCATION |