Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2009 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/22/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED BACKING FOR DRYWALL AT END OF TUB SURROUND (VERTICAL) BOTH BATH'S 2) BLOCK 3 SIDES MECH DUCT MASTER BATH 3) LARGE CLOSET NEXT TO MASTER BED CEILING LIGHT 12" FROM SHELF 4) SOFFITS IN GARGE NOT SECURE 5) CHECK ALL PIPES AND WIRES FOR NAIL PROTECTION (DRYWALL) 6) LOOSE PLATE STUD NORTH OF FRONT DOOR 7) STUD CUT AT OVEN VENT 8) ARE PIG TAIL CONNECTORS APPROVED ? KIT 4 SQUARE BOX CLEAN UP WIRING 9) LARGER SPLICE ON VERT JOINTS STUCCO LATH 10) 15" TO CENTER TOILET AT HALL BATH, 12" PEX TO CAN LIGHT 11) STOPPED INSPECTION HAD AN APPT. 12) NEED TO CHECK INSIDE OF PARAPET WALL, RAINING TO HARD TO GET ON ROOF |
|
| 01/20/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH NAILING OFF MESH 2) BROKEN WINDOW NORTHWEST CORNER IN DINING ROOM 3) MAKE UP CEILING OUTLET IN DINING ROOM 4) NAIL PROTECTION NEEDED ON KITCHEN VENT PIPE 5) FILL IN SHOES OF TUBS IN CEMENT 6) BLOCK BOOTS OF DUCT WORK A MINIMUM OF 3 SIDES 7) MINIMUM 12" CLEARANCE FROM PEX LINE TO RECESSED CAN LIGHT |
|
| 11/13/2008 | FRAMING | Partial Approval | IVRS - Inspection :* 1) PORCH |