Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/10/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL CLEANOUTS REQUIRE THREAD SEALANT LAV. FAUCET, STRAINERS AND CARRIERS NOT PER PLAN |
|
| 10/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CLOSET FLANGES OK FACTORY TAPPED PLUGS INSTALLED OK 1. CALL IN AND HAVE ALL PLUMBING INSPECTIONS APPROVED 2. COMPLETE INSTALL OF TRAP PRIMERSS WITH ACCESS 3. MAKE ALL FIXTURES WATER TIGHT 4. SUPPORT & SECURE EXPANSION TANK LIST MAY NOT BE COMPLETE CALL IN AND HAVE APPROVED ALL PLUMBING INSPECTION |
|
| 09/10/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PVC WATER LINE AROUND EXTERIOR, OK TO COVER AFTER REMOVING ROCKS. REDLINE PLANS FOR CHANGE REMOVE CO COVERS FOR INSP OF PLUGS SECURE CLOSET FLANGES TEMP LIMITING VALVES REQUIRED FOR LAVS EXP TANK REQUIRED AT WH WH VALVE SHALL BE FULL WAY PAINT EXPOSED VENTS TRIM OUT EXT. CLEANOUTS |
|
| 07/30/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - ACCESS DOORS SHALL BE PROVIDED AT CO IN MENS LAV AND CO LEFT OF URINAL. - TEST TEE BEHIND MENS WC WILL BE TRIMMED OUT AS A CO |