Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/30/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS. RECALL INSP. FOR CLOSET FLANGES AFTER FINISHED FLOOR |
|
| 07/26/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DWV LEAKING. CORRECT LEAK. TEST. THEN CALL FOR INSPECTION. YOU WILL BE CHARGED A REFEE IF YOU FAIL NEXT INSP. RECIRC LINE NOT SHOWN ON PLAN, REDLINE INSTALLATION ON PLAN. |
|
| 07/25/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - DWV NOT UNDER TEST. ALSO, SUPPORT END OF LINE C.O - HOT WATER RECIRC DOES REQUIRE PIPE INSULATION - WILL ACCESS DOOR BEHIND WOMENS TOILET OPEN TO ALLOW CLEARANCE TO 4" CO? - IF NOT CORRECT, NEED TO SEE PLANS FOR HW SYSTEM |
|
| 07/24/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/23/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* -- WATER PIPING NOT SIZED PER PLAN. NOT PER SPEC. -- TRAP PRIMER AND HAMMER ARRESTOR NOT INSTALLED PER PLAN -- WATER PIPING NOT INSTALLED PER CODE -- READ AND COMPLY W/UPC SECTIONS 606 & 609 ALSO, SEE I S #3 -- ALL JOINTS SHALL BE REAMED AND WIPED CLEANOUTS CANNOT OPEN BELOW FLOW LINE SWEEP REQUIRED ON VERT X HORIZ VENT NOT PER PLAN USE APPROVED SUPPORTS |
|
| 07/16/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE TEST ON ALL WATER, WASTE AND VENT THROUGH ROOF. 2. PROVIDE SUPPORT ON ALL PIPE 3. PROVIDE FALL ON WASTE PIPING FOR LAVS 4. INSTALL WATER PIPING FOR TRAP PRIMER PER DETAIL 205 5. PROVIDE ACCESS TO CLEANOUTS FOR WATER CLOSURES. |