Permit: T06CM06291

Parcel: 127090150


Addresses:

122 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/10/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/30/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
OK TO COVER
RECALL 03005 FOR PRE-SLAB INSPECTION PRIOR TO CONCRETE
03/29/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. 10' WATER TEST REQUIRED
2. SUPPORT WC TRAP ARM
3. PLANS REQUIRED FOR INSP
4. IF YOU INSTALL YOUR FD'S AND FOAM WRAPS IT WILL SAVE YOU FROM NEEDING A PRE-SLAB INSP.
03/27/2007 PLUMBING - ROUGH, SOIL Denied 1. 4" CO SHOWN AT P-2, 3" CO DOES NOT SERVE A 4" WASTE
2. DOUBLE FIXTURE FITTING REQUIRED AT DBL FIXTURE CONNECTION. WCS
3. THREAD FOR ABS CANNOT BE CONCEALED
4. POLY SLEEVE DOES NOT PROVIDE PROPER PROTECTION OF PEX TUBING PASSING THROUGH CONCRETE.