Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 03/30/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* OK TO COVER RECALL 03005 FOR PRE-SLAB INSPECTION PRIOR TO CONCRETE |
|
| 03/29/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. 10' WATER TEST REQUIRED 2. SUPPORT WC TRAP ARM 3. PLANS REQUIRED FOR INSP 4. IF YOU INSTALL YOUR FD'S AND FOAM WRAPS IT WILL SAVE YOU FROM NEEDING A PRE-SLAB INSP. |
|