Permit: T06CM06291

Parcel: 127090150


Addresses:

122 N CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ROOFTOP GFI RECEPTACLE HAS NO POWER
2. SHORT ON WIRES TO AC DISCONNECT
09/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL SERVICE RECEPTACLE FOR AC UNITS ON ROOF
2. INSTALL 2 POLE 20 AMP BREAKER FOR WATER HEATER
3. INSTALL SERVICE DISCONNECTS FOR FAN COIL UNITS
4. INSTALL SINGLE POLE BREAKERS FOR AC UNITS
5. INSTALL 2 POLE 60 AMP BREAKER FOR FEED TO
NEW PANEL "PA"
6. NEUTRAL TO BE #6 TO NEW PANEL
7. PROVIDE REVISION FOR CHANGES TO DRAWING