Permit: T06CM06287

Parcel: 11521017H

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06287

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
10/16/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. ALL DRAINS SHALL DISCHARGE SO AS TO PREVENT SPLASHING OR FLOODING
2. SINKS SHALL HAVE GRATES AND STRAINERS
3. REMOVE TEST PLUGS AND INSTALL COUNTER SUNK, TAPPED CLEANOUT PLUGS W/CHROME PLATED COVERS
4. DRAINS FROM CHAIRS TO HAVE 1/4" PER FOOT PITCH
09/10/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. NO RECIRCULATING SYSTEM ON THIS PROJECT. INSTALL PER 2003 I.E.C.C (MODEL ENERGY CODE) FOR DOMESTIC HOT WATER SYSTEMS.
2. SUPPORT ABS AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS.
3. DID NOT LOCATE THERMOSTAT MIXING VALVE, AS REQUIRED BY DETAIL 205 ON P2
4. OK TO COVER PONY WALLS AT BACKFLOW DEVICE AREAS
5. PLEASE CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL
6. THE WATER HEATER SHALL NOT BE THE SOLE SOURCE OF HEAT CONTROL FOR PUBLIC USE LAVATORIES.