Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM06287
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/01/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 10/16/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. ALL DRAINS SHALL DISCHARGE SO AS TO PREVENT SPLASHING OR FLOODING 2. SINKS SHALL HAVE GRATES AND STRAINERS 3. REMOVE TEST PLUGS AND INSTALL COUNTER SUNK, TAPPED CLEANOUT PLUGS W/CHROME PLATED COVERS 4. DRAINS FROM CHAIRS TO HAVE 1/4" PER FOOT PITCH |
|
| 09/10/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NO RECIRCULATING SYSTEM ON THIS PROJECT. INSTALL PER 2003 I.E.C.C (MODEL ENERGY CODE) FOR DOMESTIC HOT WATER SYSTEMS. 2. SUPPORT ABS AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. 3. DID NOT LOCATE THERMOSTAT MIXING VALVE, AS REQUIRED BY DETAIL 205 ON P2 4. OK TO COVER PONY WALLS AT BACKFLOW DEVICE AREAS 5. PLEASE CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL 6. THE WATER HEATER SHALL NOT BE THE SOLE SOURCE OF HEAT CONTROL FOR PUBLIC USE LAVATORIES. |