Permit: T06CM06287

Parcel: 11521017H

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06287

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/31/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED NO ACCESS 4:45 PM
10/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1. DISCONNECT FOR EX. FAN ON ROOF STILL IS NOT GROUNDED OR IDENTIFIED WITH SPACE OR PANEL NUMBER
YOU WILL NEED TO PAY A REINSPECTION FEE BEFORE FINAL APPROVAL. MAKE SURE CORRECTION IS MADE BEFORE YOU CALL FOR REINSPECTION
10/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
09/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ON ROOF - IDENTIFY & GROUND EX. FAN DISCONNECT PROVIDE PROPER SIZE FUSES AND MAKE SURE MOTOR IS WIRED PROPERLY (FUSE BLOWN)
2. INSTALL DRYWALL & ACCESS COVERS AT SPA'S
3. PANEL DIRECTORY TO BE PROPERLY IDENTIFIED
08/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no plan or job inspection card on site.| 925*
NEED APPROVED PLANS BEFORE YOU CALL FOR FINAL