Permit: T06CM06287

Parcel: 11521017H

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM06287

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/06/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WALLS COVERED PRIOR TO APPROVAL REMOVE FOR INSPECTION.
03/29/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. MC CABLE CANNOT BE INSTALLED WITHIN 1 1/4" FROM FACE OF STUD DUE TO POSSIBLE SCREW DAMAGE.
2. 12X12 J-BOX AT FRONT OF SPACE ABOVE CEILING HAS MULTIPLE UNSUPPORTED CABLES & FLEX ALSO, ABOVE PANEL IN BACK SUPPORT PER NEC
03/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER EXCEPT WAXING & STORAGE ROOMS
WHERE SWITCHES ARE LOCATED
SWITCHES NOT INSTALLED AT THIS TIME.
03/12/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
BUILDING LOCKED