Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06287
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/05/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* WALLS COVERED PRIOR TO APPROVAL REMOVE FOR INSPECTION. |
|
| 03/29/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MC CABLE CANNOT BE INSTALLED WITHIN 1 1/4" FROM FACE OF STUD DUE TO POSSIBLE SCREW DAMAGE. 2. 12X12 J-BOX AT FRONT OF SPACE ABOVE CEILING HAS MULTIPLE UNSUPPORTED CABLES & FLEX ALSO, ABOVE PANEL IN BACK SUPPORT PER NEC |
|
| 03/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER EXCEPT WAXING & STORAGE ROOMS WHERE SWITCHES ARE LOCATED SWITCHES NOT INSTALLED AT THIS TIME. |
|
| 03/12/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* BUILDING LOCKED |