Permit: T06CM06275

Parcel: 132166460


Addresses:

945 E OHIO ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06275

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/27/2008 ELECTRIC - FINAL Approved
04/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK SUMP PUMP
04/03/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- NEED TO CONSULT WITH SUPERVISOR FOR RESPONSE FROM ARCH. CONCERNING GARAGE COMPACTORS
- NEED COPY OF TRANSFER SWITCH TEST OPERATION
- EGRESS FOR ELECTRIC ROOM NOT RESOLVED YET
03/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- NEED TO RESOLVE EGRESS ISSUE IN ELECTRIC ROOM, PANIC HARDWARE
- TRASH COMPACTOR NOT CONNECTED YET
- EVERYTHING ELSE OK
03/20/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED BY CONTRACTOR
03/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NOT COMPLETE: ELECTRIC GATES, GARBAGE COMPACTORS, SURVEILLANCE CAMERAS, POWER POLES IN #131, CUSTOMER SERVICE AREA LV, CSO TECH AREA #215, TELECOM ROOM #157
ELEC. GENERATOR ROOM NEEDS 2ND EGRESS AND PANIC HARDWARE PER 110.26C NEC

RECEIVED EM. GENERATOR TEST INFO.